Refrigerant Charge
Unit Size
Charge
oz. (kg.)
Additional Charge
Required After ft. (m)
Additional Charge
oz./ft. (g/m)
Metering Device
18 K 47.6 (1.35) 20 (6.1) 0.21 (20) EXV
24 K 77.6 (2.2) 30 (9.1) 0.21 (20) EXV
30 K 77.6 (2.2) 40 (12.2) 0.21 (20) EXV
36 K 102.2 (2.9) 40 (12.2) 0.235 (22) EXV
42 K 169.3 (4.8) 150 (45.7) 0.235 (22) EXV
NOTES:
EXV = Electronic Expansion Device
Electronic expansion valves in the outdoor unit are used as metering devices.
Electrical Data
Unit Size
System Voltage
V o l t s --- P h --- F r e q
Operating Voltage
(Min/Max)
MCA
Max
Fuse/CB Amps
(MOCP)
18K 208/230---1---60 187/253 13 20
24K 208/230---1---60 187/253 20 30
30K 208/230---1---60 187/253 26 45
36K 208/230---1---60 187/253 28 45
42K 208/230---1---60 187/253 29 50
CAUTION
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
S Wires should be sized based on NEC and local codes.
S Use copper conductors only with a minimum 300 volt .
rating and 2/64 inch thick insulation.
CAUTION
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage
or improper operation.
S Be sure to comply with local codes while running wire from
indoor unit to outdoor unit.
S Every wire must be connected firmly. Loose wiring may
cause terminal to overheat or result in unit malfunction. A
fire hazard may also exist. Therefore, be sure all wiring is
tightly connected.
S No wire should be allowed to touch refrigerant tubing,
compressor or any moving parts.
S Disconnecting means must be provided and shall be located
within sight and readily accessible from the air conditioner.
S Connecting cable with conduit shall be routed through hole
in the conduit panel.
Connecting (Power and Control
Cable)
S The main power is supplied to the outdoor unit. The field
supplied connecting cable from the outdoor unit to indoor unit
consists of four wires and provides the power for the indoor unit
as well as the communication signal and ground between the
outdoor and indoor unit.
Two wires are high voltage AC power, one is low voltage DC
signal and one is a ground wire.
S Consult local building codes, NEC (National Electrical Code) or
CEC (Canadian Electrical Code) for special requirements.
S Wires should be sized based on NEC and local codes.
S Connecting Cable: Voltage drop on the connecting cable should
be kept to a minimum. Do not use thermostat wire. Solid or
stranded cables can be used.